Not your fault
By Howard Johnson, PhD -- 3/5/2009
Have you every turned on a light switch, only to see a bright flash just before the whole room plunges into darkness? You just tripped a circuit breaker. That failure scenario requires a light-bulb filament that has almost, but not quite, burned through. When you apply power to the bulb for the last time, a rapid wave of heat stress breaks the filament, sending fragments of broken filament flying around inside the bulb. A short fragment lodges across the power terminals inside the bulb, shorting those terminals together. In that shorted condition, the bulb draws far more current than its designed operating level. The filament shines blindingly white-hot in its last moment before the building circuit breaker pops, disconnecting power to the bulb. This scenario may sound unlikely, but you’ve probably seen it happen.
In the brief moment before the circuit breaker pops, the power-circuit load comprises three things in series: the hot wire leading to the bulb, the shorted bulb, and one neutral wire coming back (Figure 1). In the worst case, a voltmeter touching points A and B could read a voltage drop as high as 60V rms. Under those conditions, the wiring easily dissipates enough power to burst the wiring into flames and toast your whole building. The circuit breaker prevents that scenario.
In addition to circuit breakers, most civilized nations require the use of modern, three-pronged grounding outlets. In that application, only the hot and neutral wires carry power currents. The green safety wire, or “third wire,” merely connects the metallic chassis of each product to earth at the ac power entrance. Under ideal, no-fault conditions, the green safety wire carries no current. An inexperienced designer might therefore conclude that the green wires form a single-point-ground reference system that provides a consistent voltage reference between different ac-powered products. It does not serve that function (Figure 2).
The box on the right represents an old vending machine with a metal body. One day, a hot wire inside the machine accidentally breaks free. It touches the metallic chassis, creating a potentially dangerous situation. Immediately, the product’s green safety wire conveys a large fault current back to the power source. That action is the sole function of the green wire. The fault current trips the circuit breaker, shutting off power and possibly saving the life of the next person who wants a candy bar.
Suitable architectures for interchassis data transfer that can easily sustain 60V rms without disruption include well-balanced, transformer-isolated standards, such as Ethernet; fiber-based optical links; free-space IR (infrared) optics; and RF transceivers. You should use interfaces such as RS-422 that lack large common-mode immunity only between equipment that permanently connects to a common outlet or power strip.
| Author Information |
| Howard Johnson, PhD, of Signal Consulting, frequently conducts technical workshops for digital engineers at Oxford University and other sites worldwide. Visit his Web site at www.sigcon.com or e-mail him at howie03@sigcon.com. |